PF307S-50-100 3PH DELTA COMMERCIAL/INDUSTRIAL FILTER SINGLE STAGE / CHASSIS MOUNT
SPECIFICATIONS
Max Voltage: 0-520VAC
Max Current: 50A/line
Usable Frequency: 50/60/400HZ
Operating Temp.: -40 TO 50C
Leakage Current (250V/60HZ): <1mA
Typ. Weight, LB(Kg): 5.3(2.4)
Climatic Class: 25/100/21
Designed And Manufactured In Accordance With The Following Standards:
EN60939-3
CSA22.2 NO. 8
Lv Directive
DOWNLOAD SHEET
TYPICAL INSERTION LOSS, 50/50 OHM
FREQ(HZ)
150K
500K
1M
10M
30M
CM,dB
64
72
68
62
45
DM, dB
58
72
76
70
62